Hager 4 Pole 16A 100MA RCBO

Archi­tec­ture

  • Curve C

  • Neutral posi­tion Right

  • Type of pole 4P

  • Number of protected poles 4

Capa­city

  • Number of modules 4

Safety

  • Residual current type A

  • Ingress Protec­tion (IP) class IP20

Voltage

  • Type voltage supply AC

  • Rated oper­a­tional voltage Ue 230 - 415 V

  • Rated insu­la­tion voltage Ui 500 V

  • Dielec­tric strength value of power frequency 2 kV

  • Rated impulse with­stand voltage Uimp 4000 V

  • Over­voltage category according to IEC 60947-1 3

Main elec­trical attrib­utes

  • Rated short-­cir­cuit breaking capa­city Icn AC according to IEC 60898-1 6 kA

  • Nominal tight­ening torque top terminal 2 - 2 Nm

  • Nominal tight­ening torque down terminal 2 - 2 Nm

Frequency

  • Frequency 50 - 50 Hz

Connec­tion

  • Cross-sec­tion of input with screws, for flex­ible conductors 1 - 16 mm²

  • Cross-sec­tion of input with screws, for massive conductors 1 - 25 mm²

Install­a­tion, mounting

  • Nominal tight­ening torque 2 - 2 Nm

  • 360° mounting posi­tion possible Yes

  • Type of top connec­tion for modular devices Screw terminal

  • Type of bottom connec­tion for modular devices bicon­nect, Bypass

Use condi­tions

  • Class of energy limit­a­tion I²t 3

  • Oper­ating temper­ature -25 - 40 °C

Dimen­sions

  • Height 84 mm

  • Width 71 mm

  • Depth 70 mm

Power

  • Total power loss under IN 10,90 W

Click here fir Data Sheet

SKU AEM416T
Brand Hager

Be The First To Review This Product!

Help other Alstra Electrical Wholesalers users shop smarter by writing reviews for products you have purchased.